Option 6 Send all zone restores when disarmed - If this option is off, the dialler will send all zone restores as
they occur. If the option is on, the dialler will send all zone restores only when the panel is disarmed. If
the option is On, only one restore will be sent for each zone that activates regardless of whether the
zones can send multiple alarm reports. If you do not want to get multiple alarms with only one restore
on disarming then you should turn off option 1 at addresses P451E-P470E (ie disable multiple
reporting).
P775E Area "B" Reporting Options - (see above for details)
P875E Area "C" Reporting Options - (see above for details)
P975E Area "D" Reporting Options - (see above for details)
AREA “A” DIALLER ACCOUNT NUMBER - P676E
AREA “B” DIALLER ACCOUNT NUMBER - P776E
AREA “C” DIALLER ACCOUNT NUMBER - P876E
AREA “D” DIALLER ACCOUNT NUMBER - P976E
The account number is a four digit number that is sent every time the dialler reports alarms in Contact ID or 4+2
mode. The special characters of B,C,D,E & F can be programmed as any of the 4 digits of the account code (see
chart on page 62 for details).
AREA “A” ARM/DISARM REPORTING SCENARIO NUMBER - P677E
AREA “B” ARM/DISARM REPORTING SCENARIO NUMBER - P777E
AREA “C” ARM/DISARM REPORTING SCENARIO NUMBER - P877E
AREA “D” ARM/DISARM REPORTING SCENARIO NUMBER - P977E
The Arm/Disarm Scenario number is the telephone number or numbers that the panel will report to when sending
the Arm & Disarm signals for each Area.
AREA “A” LATCHKEY DISARM REPORTING SCENARIO NUMBER - P678E
AREA “B” LATCHKEY DISARM REPORTING SCENARIO NUMBER - P778E
AREA “C” LATCHKEY DISARM REPORTING SCENARIO NUMBER - P878E
AREA “D” LATCHKEY DISARM REPORTING SCENARIO NUMBER - P978E
The Latchkey Disarm Scenario number is the telephone number or numbers that the panel will report to when
sending the Disarm signal following a Latchkey disarm. The format that the panel will send is also programmable
via the telephone number/s used e.g. this report would most likely use the Voice reporting format.